- UL Type USE-2 / RHH / RHW-2 conductors are used in conduit and direct burial (as UL Type USE-2) for services, feeders, and branch circuits in residential, commercial or industrial applications in accordance with the NEC. When used as UL Type USE-2 or RHW-2, the conductor is suitable for use in dry or wet locations at temperatures not to exceed 90°C. When used as UL Type RHH, the conductor is suitable for use in dry locations at temperatures not to exceed 90°C. The conductor is rated 600 V.
- Conductors:
- Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
- Insulation:
- Abrasion, moisture, heat, and sunlight resistant colored crosslinked polyethylene (XLPE).
- Assembly:
- Cabled assembly of 2 phase conductors and 1 neutral conductor.
- Phase Conductors: Black with phase identification (“Phase A”, “Phase B”)
- Neutral Conductor: Black with three yellow stripes
- Overall Diameter Less than or Equal to 1.000 in
- Not Under Tension: 4x outer diameter
- Under Tension (During Pull): 6x outer diameter
- Overall Diameter Greater than 1.000 in
- Not Under Tension: 5x outer diameter
- Under Tension (During Pull): 7.5x outer diameter
- Sunlight resistant and marked
- RoHS Compliant
- ASTM B800 -- 8000 Series Aluminum Alloy Wire for Electrical Purposes—Annealed and Intermediate Tempers
- ASTM B801 -- Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
- UL 44 -- Thermoset-Insulated Wires and Cables (RHH / RHW-2)
- UL 854 -- Service-Entrance Cables (USE-2)
- ICEA S-95-658 / NEMA WC70 -- Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- Federal Specification AA-59544
- Federal Specification JC-30B
- UL listed as Type USE-2 -- File E487841
- UL listed as Type RHH / RHW-2 -- File E487972