As flame-retardant multi-conductor control, signal or power cables rated 600 volts, 90 ºC in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class I remote-control and signaling circuits per Article 725 of the NEC. Type TC-ER cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.
Stranded uncoated copper conductors, 30 mils XLPE crosslinked polyethylene insulation, color coded, two conductors flat, three or more conductors twisted with suitable fillers where necessary to make round, cable tape, CPE jacket overall, surface printed.
These conductors are manufactured and tested to meet or exceed the following standards:
Listed by UL as Type TC-ER per Standard 1277 for Tray Cables.
Cables meet requirements of ICEA S-73-532, NEMA WC70 for Control Cables.
E1 or E2 color codes
PVC jacket
Overall copper tape shield
Consult AWG for a variety of alternate constructions for specific applications.
USA
28-Aug-25
Control Cable
Notes:
Cables may be supplied with an insulated ground and marked "Open Wiring."
Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73-532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.
Color Coding also available ICEA Method 1, Table E-1; power sizes, ICEA Method 4.